ABUS TECHNOLOGIES INC.
15
A9696
functions 0 to 5 only; on the other hand, I/05 can perform all 16 functions). The description for the
functions follows:
CODE 0: No function - The I/O channel programmed with code 0 will not be used
by the controller. It is available to be used by serial
communication as digital output.
CODES 1 to 4: Alarm output - Available for all I/O channels. The selected channel can be
used as output to Alarms 1 to 4.
CODE 5: PWM control output - Available for all I/O channels.
CODE 6: Digital input - Available for I/O5 and I/O6 channels and key
F
.
Closed: Manual control
Opened: Automatic control
I/O channel functions
CODE I/O TYPE I/O FUNCTION
0
Digital Output Digital Output to be set by the serial comm.
1
Digital Output Alarm 1 Output
2
Digital Output Alarm 2 Output
3
Digital Output Alarm 3 Output
4
Digital Output Alarm 4 Output
5
Digital Output PWM Control Output
6
Digital Input Automatic/Manual mode change
7
Digital Input Run/Stop mode change
8
Digital Input Select Remote Set Point Input
9
Digital Input Executes/Holds selected ramp and soak profile
10
Digital Input Enable/Disable R&S profile 1 selection
11
Analog Output 0 ~ 20mA Analog control output
12
Analog Output 4 ~ 20mA Analog control output
13
Analog Output 0 ~ 20mA PV retransmission
14
Analog Output 4 ~ 20mA PV retransmission
15
Analog Output 0 ~ 20mA SP retransmission
16
Analog Output 4 ~ 20mA SP retransmission